Home >> Products >> 72
ABB Inverter ACS800-01-0120-7
Product Name: Inverter.
Model: ACS800-01-0120-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 113A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 172A.
Typical motor power in no-overload use: 110KW
Frame size: R6.
Typical motor power in light-overload use: 90Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 86A.
Typical motor power in heavy-duty use: 75KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 108A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Mitsubishi Inverter FR-F740-S132K
Product Name: Inverter.
Model: FR-F740-S132K.
132 KW.
Rated voltage: Three-phase 380 to 500 V.
Applicable motor capacity: 132 kW.
Permissible AC voltage fluctuation: 323 to 528V 50Hz/60Hz.
Power supply capacity: 198 kVA
Cooling system: Forced air cooling.
Approx. mass: 72 Kg.
ABB Inverter ACS800-01-0025-2
Product Name: Inverter.
Model: ACS800-01-0025-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 72A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 86A.
Typical motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 69A.
Typical motor power in light-overload use: 18.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 11KW.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 49A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
254 Results 12/Page Page 18 of 22     [First Page] << Previous 14 15 16 17 18 19 20 21 22 Next >>