Home >> Products >> 55
ABB Inverter ACS800-01-0205-3
Product Name: Inverter.
Model: ACS800-01-0205-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 290A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 351A.
Typical motor power in no-overload use: 160KW
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in light-overload use: 160Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 234A.
Typical motor power in heavy-duty use: 132KW.
Frame size: R6.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 285A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS550-01-125A-4
Product Name: Inverter.
Model: ACS550-01-125A-4.
3-phase supply voltage 380 to 480 V.
Wall-mounted units.
Typical motor power in 400 V at normal use: 55kw.
Continuous rms current. 50% overload is allowed for one minute in ten minutes: 96A.
Continuous rms current. 10% overload is allowed for one minute in ten minutes: 125A.
Typical motor power in 400 V at heavy-duty use: 45KW.
Typical motor power in 460 V at heavy-duty use: 75HP.
Typical motor power in 460 V at normal use: 100hp.
Frame size: R5.
ABB Inverter ACS550-01-05A4-4
Product Name: Inverter.
Model: ACS550-01-05A4-4.
3-phase supply voltage 380 to 480 V.
Continuous rms current. 10% overload is allowed for one minute in ten minutes: 5.4A.
Typical motor power in 400 V at normal use: 2.2kw.
Typical motor power in 460 V at normal use: 3hp.
Wall-mounted units.
Typical motor power in 400 V at heavy-duty use: 1.5KW.
Typical motor power in 460 V at heavy-duty use: 2HP.
Continuous rms current. 50% overload is allowed for one minute in ten minutes: 4.1A.
Frame size: R1.
ABB Inverter ACS355-03X-38A0-4
Product Name: Inverter.
Model: ACS355-03X-38A0-4.
3-phase AC supply, 380 to 480 V.
Typical motor power in 400 V at normal use: 18.5kw.
Current rating represents the rated continuous drive output current inside the drive specification.
Continuous rms current. 50% overload is allowed for one minute in ten minutes: 38.0A.
Frame size: R4.
Typical motor power in 460 V at normal use: 25.0hp.
ACS355 is available in two voltage ranges: 2 = 200 to 240 V and 4 = 380 to 480 V.
This code states the factory installed SW variants to the drive.
Mennekes AMAXX receptacle combination 930632
Product Name:AMAXX? receptacle combination
Part No.:930632.
Fitted with:2 CEE 32A, 5p, 400V
2 french/belg. standard 16A, 2p+E, 230V.
Fusing:1 RCD 63A, 4p, 0.03A
2 MCB′s 32A, 3p+N, C
2 MCB′s 16A, 1p+N, C
Pre-fuse max:63A.
InA :44A.
RDF:0.55.
Connection/feeder cable:for 2 cable up to 5 x 25mm2.
Enclosure size:390 x 225 mm (H x W).
Protection type IP44.
pre-wired for installation.
hinged to the side.
enclosure and insert made of AMAPLAST.
fusing behind a transparent cover.
Mennekes Connector AM-TOP 557
Product Name:Connector AM-TOP?
Part No.:557.
Ampere:32A.
Poles:4p
Voltage:500V.
Earth position:7h.
Hertz 50-60Hz.
Connection technology:screw terminals.
Contact:standard.
Protection type IP67.
screw terminals.
single part body.
cable gland and sealing.
strain relief and protection against kinking.
611 Results 12/Page Page 14 of 51     [First Page] << Previous 10 11 12 13 14 15 16 17 18 19 Next >> [Last Page]