ABB Inverter ACS800-01-0025-2
Product Name: Inverter.
Model: ACS800-01-0025-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 72A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 86A.
Typical motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 69A.
Typical motor power in light-overload use: 18.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 11KW.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 49A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0030-2
Product Name: Inverter.
Model: ACS800-01-0030-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 86A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Typical motor power in heavy-duty use: 15KW.
Typical motor power in no-overload use: 22KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 80A.
Typical motor power in light-overload use: 22Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 60A.
Phd: 112A.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0040-2
Product Name: Inverter.
Model: ACS800-01-0040-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 103A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 138A.
Typical motor power in no-overload use: 30KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 94A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 69A.
Typical motor power in heavy-duty use: 18.5KW.
Frame size: R5.
Typical motor power in light-overload use: 22Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0050-2
Product Name: Inverter.
Model: ACS800-01-0050-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 141A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 164A.
Typical motor power in no-overload use: 37KW
Frame size: R6.
Typical motor power in light-overload use: 37Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 97A.
Typical motor power in heavy-duty use: 30KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 132A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0003-2
Product Name: Inverter.
Model: ACS800-01-0003-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 8.5A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 10.8A.
Typical motor power in no-overload use: 1.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 7.7A.
Typical motor power in light-overload use: 1.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 1.1KW.
Frame size: R2.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 5.7A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0001-2
Product Name: Inverter.
Model: ACS800-01-0001-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Frame size: R2.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 6.5A.
Typical motor power in no-overload use: 1.1KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 4.7A.
Typical motor power in light-overload use: 0.75Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 3.4A.
Typical motor power in heavy-duty use: 0.55KW.
Rated current available continuously without overloadability at 40 °C: 5.1A
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Mennekes AMAXX receptacle combination 941445
Product Name:AMAXX? receptacle combination
Part No.:941445.
Fitted with:1 CEE 32A, 5p, 400V
2 french/belg. standard 16A, 2p+E, 230V
1 CEE 16A, 2p, 20-25V.
Fusing:1 RCD 40A, 4p, 0.03A
1 MCB 32A, 3p+N, C
2 MCB′s 16A, 1p+N, C
1 single phase transformer 160VA, 230V/24V
1 MCB 6A, 2p, C
1 MCB 4A, 1p+N, C.
Pre-fuse max:40A.
InA :32A.
RDF:0.6.
Connection/feeder cable:for 1 cable up to 5 x 16mm2.
Enclosure size:520 x 225 mm (H x W).
Protection type IP44.
pre-wired for installation.
hinged to the side.
enclosure and insert made of AMAPLAST.
fusing behind a transparent cover.
Mennekes DELTA-BOX receptacle combination 92894
Product Name:DELTA-BOX receptacle combination
Part No.:92894.
Fitted with:1 CEE 16A, 5p, 400V
1 CEE 16A, 3p, 230V
1 SCHUKO? 16A, 230V.
Connection/feeder cable:for 1 cable up to 5 x 10 mm2.
Protection type:IP67.
pre-wired for installation.
with cable grip and installed hanging hook.
enclosure and insert made of AMAPLAST.
Mennekes AMAXX receptacle combination 941464
Product Name:AMAXX? receptacle combination
Part No.:941464.
Fitted with:6 french/belg. standard 16A. 2p+E, 230V.
Fusing:1 RCD 40A. 4p. 0.03A
3 MCB′s 16A, 1p+N, C
1 off button
1 indicator light.
Pre-fuse max:100A
InA :16A.
RDF:1.
Enclosure size:520 x 225 mm (H x W).
Protection type IP44.
pre-wired for installation.
hinged to the side.
enclosure and insert made of AMAPLAST.
fusing behind a transparent cover.
Mennekes Panel mounted receptacle 1594
Product Name:Panel mounted receptacle
Part No.1594.
Ampere :32A.
Poles:3P.
Voltage:20-25V.
Hertz:50-60 Hz.
Earth position:0 h.
Connection technology:Screw terminals.
Contact:standard.
Protection type:IP44.
screw terminals.
straight.
also suitable for cable ducts and flush mounted installation boxes.
Mennekes Plug PowerTOP 3944
Product Name:Plug PowerTOP?
Part No.:3944.
Ampere:32A.
Poles:3p.
Voltage:400V.
Earth position:9h.
Hertz 50-60Hz.
Connection technology:screw terminals.
Contact:nickel plated contacts, highly heat resistant contact carrier.
Protection type IP44.
screw terminals.
highly heat resistant contact carrier.
nickel plated contacts.
cable gland and external cable grip.
Mennekes Panel mounted receptacle 1494
Product Name:Panel mounted receptacle
Part No.:1494.
Ampere:32A.
Poles:4p.
Voltage:110V.
Earth position :4h.
Hertz 50-60Hz.
Connection technology:screw terminals.
Contact: standrad.
Protection type IP44.
screw terminals.
suitable for through wiring.
20° inclination.
receptacles optional fitted with auxiliary contact.