Home >> Products >> ACS800-01-00
ABB Inverter ACS800-01-0005-5
Product Name: Inverter.
Model: ACS800-01-0005-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 6.2A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 8.2A.
Typical motor power in no-overload use: 3KW
Frame size: R2.
Typical motor power in light-overload use: 3Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 4.2A.
Typical motor power in heavy-duty use: 2.2KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 5.6A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0005-3
Product Name: Inverter.
Model: ACS800-01-0005-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 8.5A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 10.8A.
Typical motor power in no-overload use: 3KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 7.7A.
Typical motor power in light-overload use: 3Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 5.7A.
Typical motor power in heavy-duty use: 2.2KW.
Frame size: R2.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0002-2
Product Name: Inverter.
Model: ACS800-01-0002-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 6.5A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 8.2A.
Frame size: R2.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 6.0A.
Typical motor power in light-overload use: 1.1Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 4.3A.
Typical motor power in heavy-duty use: 0.75KW.
Typical motor power in no-overload use: 1.5KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0025-7
Product Name: Inverter.
Model: ACS800-01-0025-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 25A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 38A.
Typical motor power in no-overload use: 22KW
Frame size: R4.
Typical motor power in light-overload use: 18.5Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 19A.
Typical motor power in heavy-duty use: 15KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 23A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0016-7
Product Name: Inverter.
Model: ACS800-01-0016-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 17A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 19A.
Typical motor power in no-overload use: 15KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Typical motor power in light-overload use: 11Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 11A.
Typical motor power in heavy-duty use: 7.5KW.
Frame size: R4.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 15A.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0006-2
Product Name: Inverter.
Model: ACS800-01-0006-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 24A.
Typical motor power in no-overload use: 4KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 18A.
Typical motor power in light-overload use: 4Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 14A.
Typical motor power in heavy-duty use: 3KW.
Frame size: R3.
Rated current available continuously without overloadability at 40 °C: 19A
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0009-2
Product Name: Inverter.
Model: ACS800-01-0009-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 25A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 32A.
Typical motor power in no-overload use: 5.5KW
Frame size: R3.
Typical motor power in light-overload use: 5.5Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 19A.
Typical motor power in heavy-duty use: 4KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 24A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0016-5
Product Name: Inverter.
Model: ACS800-01-0016-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 19A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 24A.
Frame size: R3.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 18A.
Typical motor power in light-overload use: 11Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 13A.
Typical motor power in heavy-duty use: 7.5KW.
Typical motor power in no-overload use: 11KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0060-5
Product Name: Inverter.
Model: ACS800-01-0060-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 79A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 112A.
Typical motor power in no-overload use: 45KW
Frame size: R5.
Typical motor power in light-overload use: 45Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 60A.
Typical motor power in heavy-duty use: 37KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 75A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0060-3
Product Name: Inverter.
Model: ACS800-01-0060-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 103A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 138A.
Typical motor power in no-overload use: 55KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 94A.
Typical motor power in light-overload use: 45Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 69A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 37KW.
48 Results 12/Page Page 3 of 4     << Previous 1 2 3 4 Next >>