Home >> Products >> 72
ABB Inverter ACS800-01-0030-3
Product Name: Inverter.
Model: ACS800-01-0030-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 55A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 72A.
Typical motor power in no-overload use: 30KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 50A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 37A.
Typical motor power in heavy-duty use: 18.5KW.
Frame size: R4.
Typical motor power in light-overload use: 22Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0120-7
Product Name: Inverter.
Model: ACS800-01-0120-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 113A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 172A.
Typical motor power in no-overload use: 110KW
Frame size: R6.
Typical motor power in light-overload use: 90Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 86A.
Typical motor power in heavy-duty use: 75KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 108A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
254 Results 12/Page Page 17 of 22     [First Page] << Previous 13 14 15 16 17 18 19 20 21 22 Next >>